Water Distribution Calculator

Design water mains and distribution systems per AWWA

Demand Information

Fire Flow Requirements

Per ISO/IFC requirements

System Configuration

During fire flow (20 PSI typical)
+ for uphill, - for downhill

Distribution Requirements

Recommended Main Size --
Peak Demand + Fire Flow --
Average Daily Demand --
Peak Hour Demand --
Velocity (Peak + Fire) --
Headloss --
Residual Pressure --
System notes will appear here.

Water Demand Factors

Use Type Average GPD Peak Factor
Single Family300-400 GPD/unit2.5-3.0
Multi-Family200-250 GPD/unit2.0-2.5
Apartment150-200 GPD/unit2.0-2.5
Office0.1-0.2 GPD/sq ft2.0
Retail0.1-0.15 GPD/sq ft1.5
Restaurant50-100 GPD/seat2.5
Hotel100-150 GPD/room2.0

Fire Flow Requirements (ISO)

Construction Type Area (sq ft) Fire Flow (GPM) Duration
1-2 Family Dwelling<3,600500-1,0001-2 hr
Small Commercial<10,0001,000-1,5002 hr
Medium Commercial10,000-50,0001,500-3,0002-3 hr
Large Commercial50,000-100,0003,000-4,0003 hr
Industrial>100,0004,000-8,0003-4 hr
Based on ISO Fire Suppression Rating Schedule. Actual requirements per local fire authority.

Design Criteria

Velocity Limits

  • Normal: 2-5 ft/s
  • Maximum: 8-10 ft/s
  • Fire flow: 10-12 ft/s
  • Avoid water hammer

Pressure Limits

  • Min static: 40 PSI
  • Max static: 80 PSI
  • Min during fire: 20 PSI
  • PRVs above 80 PSI

Pipe Sizing

  • Min residential: 6"
  • Min commercial: 8"
  • Grid/loop systems
  • Dead ends <600 ft

Appurtenances

  • Valves per 500 ft
  • Hydrant spacing: 300-600 ft
  • Air release valves
  • Blow-offs at low points