CPVC Pipe Sizing Calculator

Size CPVC piping for hot and cold water per UPC/IPC

CTS is most common for residential water supply

Fixture Count

System Parameters

Recommended Pipe Size

Minimum CPVC Size --
Flow Velocity --
Total WSFU --
Design Flow --
Friction Loss --
Pressure at Fixture --
Temperature Rating: CPVC rated to 200F at 100 PSI. Pressure rating decreases at higher temperatures.

CPVC CTS Size Reference

Nominal OD (in) ID (in) Max GPM
1/2"0.6250.4854.6
3/4"0.8750.7059.7
1"1.1250.91116.3
1-1/4"1.3751.10724.0
1-1/2"1.6251.29132.7
2"2.1251.69556.3
Max GPM based on 8 ft/s velocity limit

CPVC Pressure/Temperature Ratings

73F

400 PSI (CTS)

Cold water max

140F

200 PSI (CTS)

Normal hot water

180F

100 PSI (CTS)

High temp limit

200F

80 PSI (CTS)

Maximum rated

CPVC Installation Guidelines

Support Spacing

  • 1/2" - 3/4": 36" horizontal
  • 1" - 1-1/4": 48" horizontal
  • 1-1/2" - 2": 60" horizontal
  • Vertical: Every floor

Expansion

  • 1.2" per 100 ft per 50F
  • Use expansion loops
  • Flexible connections
  • Never force alignment

Solvent Cement

  • Use CPVC-specific cement
  • One-step or two-step
  • Full depth insertion
  • 24 hr cure before pressure