Condensate Drain Sizing Calculator

Size condensate drain lines for HVAC equipment per UPC/IMC requirements

Equipment Capacity

Drain Configuration

Drain Requirements

Minimum Drain Size --
Recommended Size --
Condensate Flow Rate --
Daily Volume --
Total Fall --
Trap Required --
Note: All condensate drains require proper slope and trap where connected to sanitary drainage.

Code Requirements (UPC/IMC)

Equipment Capacity Min Drain Size
Up to 20 tons3/4"
21-40 tons1"
41-90 tons1-1/4"
91-125 tons1-1/2"
126-250 tons2"

Installation Notes

  • Maintain minimum 1/8" per foot slope
  • Provide trap if connected to sanitary drain
  • Air gap required for indirect waste
  • Auxiliary drain pan required for attic installations
  • Consider condensate pump for negative slope situations

Condensate Production Rates

Equipment Typical Production Peak Production Notes
AC (per ton)0.5-1 gal/hr1.5 gal/hrVaries with humidity
90%+ Furnace0.5-1 gal/hr1.2 gal/hrAcidic condensate
Condensing Boiler1-3 gal/hr5 gal/hrRequires neutralizer
Dehumidifier2-8 gal/day12 gal/day70 pint unit