Backflow Testing Calculator
Enter test readings to determine pass/fail per ASSE standards
RPZ Test Readings
Must hold at 1.0 PSID min
Must hold at 1.0 PSID min
Must open at 2.0 PSID min (below CV#1)
System Pressure
Test Results
Overall Result
--
Check Valve #1
--
Check Valve #2
--
Relief Valve
--
Pressure Drop
--
Assembly Standard
--
Test result details will appear here.
Minimum Test Requirements
| Assembly | Component | Min. Requirement |
|---|---|---|
| RPZ | Check #1 | 1.0 PSID |
| Check #2 | 1.0 PSID | |
| Relief Valve | 2.0 PSID below CV#1 | |
| DC | Check #1 | 1.0 PSID |
| Check #2 | 1.0 PSID | |
| PVB/SVB | Air Inlet | 1.0 PSIG opening |
| Check Valve | 1.0 PSID |
Testing Standards & Procedures
RPZ (ASSE 1013)
- Close #2 shutoff, open test cocks
- Record CV#1 reading
- Open #2 shutoff slowly
- Record RV opening point
- Close #1 shutoff
- Record CV#2 reading
DC (ASSE 1015)
- Close #2 shutoff
- Bleed to atmosphere
- Record CV#1 reading
- Close #1 shutoff
- Open #2 shutoff
- Record CV#2 reading
PVB (ASSE 1020)
- Close downstream shutoff
- Open test cock
- Record air inlet opening
- Close test cock
- Attach gauge to body
- Record CV reading
Frequency
- Initial: At installation
- Routine: Annual minimum
- After repair: Immediate
- Records: Keep 5+ years