Backflow Preventer Selection

Select appropriate backflow assembly based on hazard and application

Application Details

High hazard: substance could cause illness or death
Backpressure: downstream pressure can exceed supply

Sizing Information

Recommended Backflow Device

Primary Selection --
Device Size --
ASSE Standard --
Pressure Loss --
Velocity --
Alternative Device --
Note: Device must be tested annually by certified tester.

Device Types

AG (Air Gap) - ASSE 1001

Physical separation, highest protection

RPBA - ASSE 1013

Reduced Pressure Backflow Assembly

DCVA - ASSE 1015

Double Check Valve Assembly

PVB - ASSE 1020

Pressure Vacuum Breaker

SVB - ASSE 1056

Spill-Resistant Vacuum Breaker

Backflow Device Selection Matrix

Application Hazard Backpressure Required Device
Fire Sprinkler (no additives)LowYesDCVA
Fire Sprinkler (w/antifreeze)HighYesRPBA
Irrigation (potable supply)HighNoPVB or SVB
Irrigation (w/chemicals)HighYesRPBA
Boiler FillHighYesRPBA
Swimming PoolHighVariesAG or RPBA
Medical/LabHighYesAG or RPBA
Commercial KitchenHighNoAVB or RPBA
Residential ServiceLowNoDCVA

Typical Pressure Loss (PSI)

Size RPBA @ rated flow DCVA @ rated flow PVB @ rated flow
3/4"12-155-88-12
1"10-144-77-10
1-1/2"8-123-66-9
2"7-113-55-8
3"5-92-4--
4"4-82-4--
6"3-61-3--
Actual pressure loss varies by manufacturer. Consult manufacturer data for sizing.