Acid Waste Piping Calculator

Size acid-resistant drainage and neutralization systems for laboratories

Laboratory Fixtures

Waste Characteristics

System Requirements

Main Drain Size --
Neutralization Tank --
Total DFU --
Branch Size --
Vent Size --
Limestone Required --
Note: All acid waste systems require separate piping and neutralization before discharge.

Piping Material Selection

Material Max Temp Best For
Polypropylene180FGeneral lab use
PVDF280FHigh purity, high temp
CPVC200FCost-effective
Borosilicate Glass450FSolvents, visibility
HDPE140FUnderground

Code Requirements

  • Acid waste must be separate from sanitary
  • Neutralization required before discharge
  • pH monitoring may be required
  • Double containment for concentrated acids
  • Fire-rated penetrations required

Neutralization Tank Sizing

Daily Flow (GPD) Min Tank Size Limestone Charge Refill Interval
< 5055 gal100 lbs6-12 months
50-150110 gal200 lbs3-6 months
150-300220 gal400 lbs2-4 months
300-500350 gal600 lbs1-3 months
> 500500+ gal800+ lbsMonthly
Tank sizing based on 30-minute retention time minimum. Actual requirements vary by acid concentration and local codes.